Technical Parameters
| Technical parameter | Parameter value |
| Moisture Temperature range | -30℃~80℃ |
| Moisture Temperature accuracy | ±0.5℃ @25℃ |
| Moisture measuring range | 0~100% |
| Moisture measuring accuracy | ±3% @25℃ |
| Communication Interface | DC4~20mA |
| Power | DC12~24V 1A |
| Running temperature | -30~80℃ |
| Working humidity | 5%RH~90%RH |
Product Size
software to test
Wiring instructions
How to use software?
Why choose this product?
How to use?
Application solution
Product List
Pictures
1. temperature and current computing relationship
For example, the range is -30~60℃, the analog output is 4~20mA current signal, temperature and current The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is temperature range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read temperature value, and C is the calculated current value. The list of commonly used values is as follows:
| current(mA) | temperatureValue (℃) | Calculation Process |
| 4 | -30 | (60-(-30))*(4-4)÷(20-4)+-30 |
| 5 | -24.375 | (60-(-30))*(5-4)÷(20-4)+-30 |
| 6 | -18.75 | (60-(-30))*(6-4)÷(20-4)+-30 |
| 7 | -13.125 | (60-(-30))*(7-4)÷(20-4)+-30 |
| 8 | -7.5 | (60-(-30))*(8-4)÷(20-4)+-30 |
| 9 | -1.875 | (60-(-30))*(9-4)÷(20-4)+-30 |
| 10 | 3.75 | (60-(-30))*(10-4)÷(20-4)+-30 |
| 11 | 9.375 | (60-(-30))*(11-4)÷(20-4)+-30 |
| 12 | 15 | (60-(-30))*(12-4)÷(20-4)+-30 |
| 13 | 20.625 | (60-(-30))*(13-4)÷(20-4)+-30 |
| 14 | 26.25 | (60-(-30))*(14-4)÷(20-4)+-30 |
| 15 | 31.875 | (60-(-30))*(15-4)÷(20-4)+-30 |
| 16 | 37.5 | (60-(-30))*(16-4)÷(20-4)+-30 |
| 17 | 43.125 | (60-(-30))*(17-4)÷(20-4)+-30 |
| 18 | 48.75 | (60-(-30))*(18-4)÷(20-4)+-30 |
| 19 | 54.375 | (60-(-30))*(19-4)÷(20-4)+-30 |
| 20 | 60 | (60-(-30))*(20-4)÷(20-4)+-30 |
As shown in the above formula, when measuring 8mA, current current is 26.5℃。
2. soil Moisture and current computing relationship
For example, the range is 0~100%, the analog output is 4~20mA current signal, soil Moisture and current The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is soil Moisture range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read soil Moisture value, and C is the calculated current value. The list of commonly used values is as follows:
| current(mA) | soil MoistureValue (%) | Calculation Process |
| 4 | 0.0 | (100-0)*(4-4)÷(20-4)+0 |
| 5 | 6.3 | (100-0)*(5-4)÷(20-4)+0 |
| 6 | 12.5 | (100-0)*(6-4)÷(20-4)+0 |
| 7 | 18.8 | (100-0)*(7-4)÷(20-4)+0 |
| 8 | 25.0 | (100-0)*(8-4)÷(20-4)+0 |
| 9 | 31.3 | (100-0)*(9-4)÷(20-4)+0 |
| 10 | 37.5 | (100-0)*(10-4)÷(20-4)+0 |
| 11 | 43.8 | (100-0)*(11-4)÷(20-4)+0 |
| 12 | 50.0 | (100-0)*(12-4)÷(20-4)+0 |
| 13 | 56.3 | (100-0)*(13-4)÷(20-4)+0 |
| 14 | 62.5 | (100-0)*(14-4)÷(20-4)+0 |
| 15 | 68.8 | (100-0)*(15-4)÷(20-4)+0 |
| 16 | 75.0 | (100-0)*(16-4)÷(20-4)+0 |
| 17 | 81.3 | (100-0)*(17-4)÷(20-4)+0 |
| 18 | 87.5 | (100-0)*(18-4)÷(20-4)+0 |
| 19 | 93.8 | (100-0)*(19-4)÷(20-4)+0 |
| 20 | 100.0 | (100-0)*(20-4)÷(20-4)+0 |
As shown in the above formula, when measuring 8mA, current current is 29%。