Technical Parameters
Technical parameter | Parameter value |
Brand | XUNCHIP |
Communication Interface | RS485 |
Default baud rate | 9600 8 n 1 |
Power | DC5~24V 1A |
Running temperature | -30~80℃ |
Working humidity | 5%RH~90%RH |
Product Size






Wiring instructions
Why choose this product?





How to use?

Application solution


Product List

Pictures



Communication Protocol
The product uses the RS485 MODBUS-RTU standard protocol format, and all operation or reply commands are in hexadecimal data. When the device leaves the factory, the default device address is 1, and the default baud rate is: for modules and non-recording instruments: 9600, 8, n, 1 (for the recorder series products, the default is: 115200, 8, n, 1).1. Read data (Function code 0x03)
The inquiry frame (in hexadecimal). Example of sending: To query 1 piece of data of device No. 1, the host computer sends the command: 01 03 00 00 00 01 84 0A .
Address | Function code | Starting address | Data length | Checksum |
01 | 03 | 00 00 | 00 01 | 84 0A |
Address | Function code | Length | Data 1 | Checksum |
01 | 03 | 02 | 02 18 | B9 2E |
2. Common Data Address Table
Configuration Address | Register Address | Register Description | Data Type | Value Range |
40001 | 00 00 | 振动传感器 | Read Only | 0~65535 |
40101 | 00 64 | Model Code | Read-only | 0~59999 |
40102 | 00 65 | Total Number of Measuring Points | Read-only | 1~1600 |
40103 | 00 66 | Device Address | Read/Write | 1~249 |
40104 | 00 67 | Baud Rate | Read/Write | 0~6 |
40105 | 00 68 | Communication Mode | Read/Write | 1 Query |
2 Active Upload | 40106 | 00 69 | Protocol Type | Read/Write |
1 MODBUS-RTU | Others Unused |