--. 0

Product

 [XM8588]  Miniature impeller wind speed sensor

XM8588

Technical Parameters

Technical parameter Parameter value
Brand XUNCHIP
Wind speed range 0~30m/s
Wind speed accuracy ±3%
Induction principle Thermal film induction
Interface RS485/4-20mA/DC0-5V/DC0-10V
Power DC12~24V 1A
Running temperature -30~80℃
Working humidity 5%RH~90%RH

Product Selection

    Product DesignRS485,4-20mA,DC0-5V,DC0-10VMultiple output methods, the products are divided into the following models depending on the output method.
Product model output method
XM8588B RS485总线
XM8588M 4-20mA
XM8588V5 DC0-5V
XM8588V10 DC0-10V

Product Size

XM8588 XM8588 XM8588 XM8588 XM8588 XM8588

Why choose this product?

XM8588 XM8588 XM8588 XM8588

How to use?

XM8588

Application solution

XM8588 XM8588 XM8588

Product List

XM8588

Pictures

XM8588 XM8588 XM8588 XM8588

Communication Protocol

    The product uses RS485 MODBUS-RTU standard protocol format, all operation or reply commands are hexadecimal data. The default device address is 1 when the device leaves the factory, and the module or NON-Recorder default baud rate is 9600,8,n,1 ,but data recorder default baud rate is 115200 .
1. Read data (function code 0x03)
    Inquiry frame (hexadecimal), sending example: query 1 data of 1# device, the upper computer sends the command: 01 03 00 00 00 01 84 0A .
Address Function Code Start Address Data Length Check Code
01 03 00 00 00 01 84 0A
    For the correct query frame, the device will respond with data: 01 03 02 02 18 B9 2E , response format:
Address Function Code Length Data 1 Check Code
01 03 02 02 18 B9 2E
    Data description: The data in the command is hexadecimal, take data 1 as an example, 02 24 is converted to decimal value as 536, assuming the data magnification is 100, then the real value is 536/100=5.36, Others and so on.
2. Common data address table
Configuration Address Register Address Register Description Data Type Value Range
40001 00 00 wind speed Read Only 0~65535
40101 00 64 Model Code Read/Write 0~65535
40102 00 65 total number of measuring points read/write 1~20
40103 00 66 device address read/write 1~249
40104 00 67 baud rate read/write 0~6
40105 00 68 communication mode read/write 1~4
40106 00 69 protocol type read/write 1~10

 

  For example, the range is 0~30m/s, the analog output is 4~20mA current signal, wind speed and current The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is wind speed range upper limit, A1 is the lower limit of the range, B2 is current output range upper limit, B1 is the lower limit, X is the currently read wind speed value, and C is the calculated current value. The list of commonly used values is as follows:
current(mA) wind speedValue (m/s) Calculation Process
4 0.0 (30-0)*(4-4)÷(20-4)+0
5 1.9 (30-0)*(5-4)÷(20-4)+0
6 3.8 (30-0)*(6-4)÷(20-4)+0
7 5.6 (30-0)*(7-4)÷(20-4)+0
8 7.5 (30-0)*(8-4)÷(20-4)+0
9 9.4 (30-0)*(9-4)÷(20-4)+0
10 11.3 (30-0)*(10-4)÷(20-4)+0
11 13.1 (30-0)*(11-4)÷(20-4)+0
12 15.0 (30-0)*(12-4)÷(20-4)+0
13 16.9 (30-0)*(13-4)÷(20-4)+0
14 18.8 (30-0)*(14-4)÷(20-4)+0
15 20.6 (30-0)*(15-4)÷(20-4)+0
16 22.5 (30-0)*(16-4)÷(20-4)+0
17 24.4 (30-0)*(17-4)÷(20-4)+0
18 26.3 (30-0)*(18-4)÷(20-4)+0
19 28.1 (30-0)*(19-4)÷(20-4)+0
20 30.0 (30-0)*(20-4)÷(20-4)+0
    As shown in the above formula, when measuring 8mA, current current is 11.5m/s。
  For example, the range is 0~30m/s, the analog output is 0~5V DC0-5Vvoltage signal, wind speed and DC0-5Vvoltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is wind speed range upper limit, A1 is the lower limit of the range, B2 is DC0-5Vvoltage output range upper limit, B1 is the lower limit, X is the currently read wind speed value, and C is the calculated DC0-5Vvoltage value. The list of commonly used values is as follows:
DC0-5Vvoltage(V) wind speedValue (m/s) Calculation Process
0 0.0 (30-0)*(0-0)÷(5-0)+0
1 6.0 (30-0)*(1-0)÷(5-0)+0
2 12.0 (30-0)*(2-0)÷(5-0)+0
3 18.0 (30-0)*(3-0)÷(5-0)+0
4 24.0 (30-0)*(4-0)÷(5-0)+0
5 30.0 (30-0)*(5-0)÷(5-0)+0
    As shown in the above formula, when measuring 2.5V, current DC0-5Vvoltage is 15m/s。
  For example, the range is 0~30m/s, the analog output is 0~10V DC0-10Vvoltage signal, wind speed and DC0-10Vvoltage The calculation relationship is as shown in the formula: C = (A2-A1) * (X-B1) / (B2-B1) + A1, where A2 is wind speed range upper limit, A1 is the lower limit of the range, B2 is DC0-10Vvoltage output range upper limit, B1 is the lower limit, X is the currently read wind speed value, and C is the calculated DC0-10Vvoltage value. The list of commonly used values is as follows:
DC0-10Vvoltage(V) wind speedValue (m/s) Calculation Process
0 0.0 (30-0)*(0-0)÷(10-0)+0
1 3.0 (30-0)*(1-0)÷(10-0)+0
2 6.0 (30-0)*(2-0)÷(10-0)+0
3 9.0 (30-0)*(3-0)÷(10-0)+0
4 12.0 (30-0)*(4-0)÷(10-0)+0
5 15.0 (30-0)*(5-0)÷(10-0)+0
6 18.0 (30-0)*(6-0)÷(10-0)+0
7 21.0 (30-0)*(7-0)÷(10-0)+0
8 24.0 (30-0)*(8-0)÷(10-0)+0
9 27.0 (30-0)*(9-0)÷(10-0)+0
10 30.0 (30-0)*(10-0)÷(10-0)+0
    As shown in the above formula, when measuring 5V, current DC0-10Vvoltage is 15m/s。
software for test product
After downloading, please read the readme.txt documentation

[RV1000] DEGBUG AND TEST SOFTWARE

Data and Software

 Online shop 

 Contact Online 

Email: sale@sonbest.com

TYPE: XM8588

WeChat: 13918126020

SKYPE: SOOBUU

Phone: +86-021-66862075

QQ1: 71182854 QQ2:613035997